You connect your gauges open up the test cocks and your gauge pegs out at 15.0 PSI.

When Testing the RP!!!

If your gauge starts acting funny by pegging out at 15 or slow to raise the needle when you open the test cocks you, before you take apart the backflow prevention assembly look at your hoses and gauge.

Try swapping the red hose for the yellow or bypass hose to see if your gauge reacts normally again so you can continue to test.

You may need to flush out the gauges and hoses or hose filters
.

The Hoses do need to be replaced to keep your equipment in good working order.Testing a new install